SPECIFIC STANDARDS:
In all areas of special flood hazard where base flood elevation data has been provided as set forth in section 12-3-2 or subsection 12-4-3B of this title, the following provisions are required:
1. Residential Construction: New construction and substantial improvement of any residential structure shall have the lowest floor (including basement) elevated to or above the base flood elevation.
2. Nonresidential Construction: New construction and substantial improvement of any commercial, industrial or other nonresidential structure shall either have the lowest floor (including basement) elevated to the level of the base flood elevation; or, together with attendant utility and sanitary facilities, shall:
1. Be floodproofed so that below the base flood elevation the structure is watertight with walls substantially impermeable to the passage of water;
2. Have structural components capable of resisting hydrostatic and hydrodynamic loads and effects of buoyancy; and
3. Be certified by a registered professional engineer or architect that the design and methods of construction are in accordance with accepted standards of practice for meeting the provisions of this subsection B3. Such certifications shall be provided to the official as set forth in subsection 12-4-3C2 of this title.
3. Openings In Enclosures Below The Lowest Floor: For all new construction and substantial improvements, fully enclosed areas below the lowest floor that are subject to flooding shall be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwaters. Designs for meeting this requirement must either be certified by a registered professional engineer or architect or must meet or exceed the following minimum criteria:
1. A minimum of two (2) openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding shall be provided.
2. The bottom of all openings shall be no higher than one foot (1') above grade.
3. Openings may be equipped with screens, louvers or other coverings or devices; provided that they permit the automatic entry and exit of floodwaters.
4. Manufactured Homes:
1. Manufactured homes shall be anchored in accordance with section 12-5-1A2 of this chapter.
2. All manufactured homes or those to be substantially improved shall be elevated on a permanent foundation such that the lowest floor of the manufactured home is at or above the base flood elevation and is securely anchored to an adequately anchored foundation system. (Ord. 88-1, 1-12-1988)